E1WF Cable Glands (Prysmian)
by Prysmian
Original price
£21.54
-
Original price
£276.00
Original price
£21.54
£21.54
-
£276.00
Current price
£21.54
Description
Prysmian E1WF Cable Glands from their KCA472 range of hazardous area cable glands suitable for terminating circular steel wire armoured cables in Zone 1 and Zone 2 locations – Prysmian E1WF cable glands provide high performance in high temperatures and achieves IP66 seal onto cable and to an enclosure with a suitable sealing washer or thread sealant.
Features & Benefits
- E1WF brass indoor and outdoor hazardous area cable gland.
- Suitable for circular armoured cables with extruded cable with extruded polymeric bedding and oversheath.
- Achieves IP66 seal onto cable and to enclosure with suitable sealing washer or thread sealant.
- Weatherproof & waterproof cable gland.
- Cable glands certified to II 2GD, Ex e II & Ex d IIC under ATEX directive 94/9/EC.
- Inner PCP seal grips cable bedding and provides additional ingress protection.
- Three part armour lock provides mechanical cable retention and electrical continuity.
- Service temperature range -60°C to +90°C.
- ATEX Compliance Standards: EN 60079-0, EN 60079-1, EN 60079-7, EN 61241-0, EN 61241-1.
- IECEx Compliance Standards: IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
- Nickel plated E1WF cable glands are available.
Applications
E1WF cable glands are suitable for use in:
Zones 0, 1 & 2 with Ex ia IIA, B & C Equipment
Zones 1 & 2 with Ex ib IIA, B & C Equipment
Zones 1 & 2 with Ex e II Equipment
Zone 2 with Ex nA II Equipment
Zones 21 & 22 with Ex tD II Equipment
Kit Contents
E1WF Gland, Brass Earth Tag, Brass Locknut, Nylon Sealing Washer, PCP Shroud. (x2 per kit up to and including 25mm size).
Directions for Use
Indoor / Outdoor Applications.
Material
Brass,
Colour
Brass
Technical Data
Type | E1WF |
---|---|
Design Specification |
BS 6121 : Part I : 1989, IEC 624444, EN62444 |
Gland Material | Brass |
Ingress Protection | IP66 |
Finish |
Plain Brass |
Seal Material |
Thermoplastic Elastomer |
Cable Type |
Armoured |
Sealing Technique | Displacement Type |
Sealing Area | Outer Sheath |
Size Chart
Gland Size | 16 | 20SS | 20S | 20 | 25 | 32 | 40 | 50S | 50 | 63S | 63 | 75S | 75 | 85 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Prysmian Part No. | KCA47271 | KCA47252 | KCA47253 | KCA47255 | KCA47256 | KCA47257 | KCA47258 | KCA47259 | KCA47260 | KCA47261 | KCA47262 | KCA47263 | KCA47264 | |
No. per Pack | x2 | x2 | x2 | x2 | x2 | x1 | x1 | x1 | x1 | x1 | x1 | x1 | x1 | x1 |
Cable Range (mm) | 8.0 - 13.2 | 8.0 - 13.2 | 8.0 - 15.8 | 11.7 - 20.8 | 17.0 - 27.2 | 23.5 - 33.5 | 29.0 - 39.9 | 38.0 - 46.2 | 39.5 - 52.6 | 50.0 - 58.9 | 51.3 - 65.3 | 62.0 - 71.6 | 62.5 - 78.0 | 68.0 - 88.0 |
Entry Thread - D (mm) | M16 x 1.5 | M20 x 1.5 | M20 x 1.5 | M20 x 1.5 | M25 x 1.5 | M32 x 1.5 | M40 x 1.5 | M50 x 1.5 | M50 x 1.5 | M63 x 1.5 | M63 x 1.5 | M75 x 1.5 | M75 x 1.5 | M85 x 1.5 |
Entry Thread - E (mm) | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 20 |
Under Armour ⌀ - A (mm) | 3.8 - 8.7 | 3.8 - 8.7 | 8.0 - 11.8 | 11.8 - 14.2 | 14.0 - 20.1 | 19.7 - 26.6 | 26.6 - 32.4 | 32.4 - 38.4 | 38.4 - 44.3 | 44.3 - 50.3 | 50.3 - 56.2 | 56.2 - 62.2 | 62.2 - 68.1 | 68.0 - 74.0 |
Armour ⌀ (mm) | 0.9 | 0.9 | 0.9/1.25 | 0.9/1.25 | 1.25/1.6 | 1.6/2.0 | 1.6/2.0 | 2.0/2.5 | 2.0/2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 3.15 |
Approx. Length from Shoulder - F (mm) | 41.0 | 41.0 | 43.0 | 43.0 | 48.0 | 53.0 | 56.0 | 61.0 | 61.0 | 64.0 | 64.0 | 73.0 | 73.0 | 102.0 |
Hexagon Across Flats - G (mm) | 23.4 | 23.4 | 25.7 | 30.5 | 37.6 | 47.2 | 26.4 | 60.0 | 70.1 | 75.0 | 80.0 | 90.2 | 98.8 | 115.1 |
Hexagon Across Corners - H (mm) | 26.7 | 26.7 | 29.2 | 34.0 | 42.2 | 53.6 | 61.5 | 66.0 | 77.2 | 83.0 | 87.4 | 99.1 | 109.2 | 126.0 |